220kV dry type plug GlS terminal
220kV dry type plug GlS terminal
+
  • 220kV dry type plug GlS terminal
  • 220kV dry type plug GlS terminal

220kV dry type plug GlS terminal

The terminal is completely dry type structure, the internal is not filled with insulating oil, overcome the stress cone by soaking in the insulating oil aging, improve the service life of the stress cone, and avoids the terminal leakage phenomenon appeared in the process of running, is both environmental protection and free maintenance.

Description

Product Features

The terminal is completely dry type structure, the internal is not filled with insulating oil, overcome the stress cone by soaking in the insulating oil aging, improve the service life of the stress cone, and avoids the terminal leakage phenomenon appeared in the process of running, is both environmental protection and free maintenance.

The combination of the spring pressing device, the application of cone surface close to the epoxy casing wall, can keep the interface pressure constant term, overcome the stress cone due to material aging phenomenon caused by the relaxation, to ensure the long-term and safe operation of the terminal.

Light weight, small size, compact structure, convenient installation and maintenance.

All the insulation parts are made of the factory, and the epoxy casing is embedded in the high pressure metal shield electrode. The rubber stress cone is used to import the high elastic liquid silicone rubber, and the structure shape of the stress cone product is optimized.

The main insulation parts have been tested in the factory according to the standard.

Products Comply With The Following Standards

GB/T18890.3-2015 Power cables with cross-linked polyethylene insulation and their accessories for rated voltage of 220 kV (Um=252kV). Part 3: Accessories

IEC 62067-2011 Power cables with extruded insulation and their accessories for rated voltages above 150kV( Um=170kV) up to 500kV (Um = 550kV). Test methods and requirements

GB/T 22381-2008 Cable connections for gas-insulated metal-enclosed switchgear for rated voltages of 72.5kV and above. Fluid-filled and extruded insulation power cables. Fluid-filled and dry type cable-terminations

IEC 62271-209-2007 High-voltage switchgear and controlgear. Part 209: Cable connections for gas-insulated metal-enclosed switchgear for rated voltages above 52kV. Fluid-filled and extruded insulation cables. Fluid-filled and dry-type cable-terminations

Main technical parameters

Item Technical parameters
Rated voltage and frequency 127/220kV, 50Hz
Max peration voltage 252kV
Environment temperature -40℃~+40℃
Rated operating temperature of conductor 90℃
Max temperature of cable conductor at short circuit 250℃
The cross section of the cable shall apply 240~2500mm²
Partial dischange test (at ambient temperature, 190kV) NO ddelectable discharge at the declared sensitivity (5pC or better)
Heating cycle voltage test (254kV, 95℃~100℃, heating 8h, cooling 16h) Completed 20 cycles
Partial dischange test (at high temperature, 190kV) NO ddelectable discharge at the declared sensitivity (5pC or better)
Impluse voltage test followed by a power frequency voltage test
- Impluse voltage test (95℃~100 C, ±1050kV, 10times, respectively)
- Power frequency voltage test (254kV, 15min)
NO breakdown or flashover
NO breakdown or flashover

Sealing test for the terminations assembled
a. Press leakage test ( (0.2±0.01 )MPa, 1h)
b. Vacuum leakage increase
-Pressure increment (B-A)

NO leakage of gas
30 Pa