CONTACT US

Jiangsu Shitate Intelligent Power Co.,LTD.

E-Mail: sttxs@jsshitate.com
Telephone: +86-18852493399

Telephone: +86-18626077857
Address: No. 5 Datian Road, Guanlin Town, Yixing City

35kV Cold Shrinkable Cable Accessories
+
  • 35kV Cold Shrinkable Cable Accessories

35kV Cold Shrinkable Cable Accessories

Advantage of using rubber "elastic memory", with advanced technology of expansion, will produce the good cable terminal rubber pieces open in advance within the elastic range, set into the plastic support. When installation, only need to remove plastic support bar, cable terminal rubber parts will rapidly shrink hold on the cable.

Description

Performance Characteristics

Cold Contracted Technology:

Advantage of using rubber "elastic memory", with advanced technology of expansion, will produce the good cable terminal rubber pieces open in advance within the elastic range, set into the plastic support. When installation, only need to remove plastic support bar, cable terminal rubber parts will rapidly shrink hold on the cable.

Reliable Insulation:

Raw material is imported from international famous companies of high quality liquid silicon rubber, reliable insulation performance, reliable and excellent electric properties. Silicone rubber materials, antistatic mark and strong corrosion resistance, long service life. Stress cone strengthened the margin design,insulation performance is more reliable.

Easy Installation:

All cable terminal rubber parts have been preformed in our factory, as long as according to the operating instructions for installation; Without professional installation tools, convenient; No flame operation, safe and reliable.

Advanced Equipment:

In purifying air conditioning workshop, cable accessories are produced by computerized automation production equipment imported from Switzerland. Based on 200 kV full screen no discharge laboratory to test the performance of cable accessories, ensure the quality of the product.

Widely use:

Because of the characteristics of the silicone rubber, flth resistance, aging resistance, good Hydrophobic performance, cold resistant performance, cable accessories are suitable for high altitude area, wet and cold areas, smog and heavy pollution areas, etc., especially suitable for petroleum, chemical industry, mining and other inflammable and explosive industries.

Products comply with the following standards

GB/T 12706.4-2020 Power cables with extruded insulation and their accessories for rated voltages from 1kV (Um=1.2kV) up to 35kV (Um=40.5kV). Part 4: Test requirements on accessories for cables with rated voltages from 6kV (Um=7.2kV) up to 35kV (Um=40.5kV).

IEC 60502-4-2010 Power cables with extruded insulation and their accessories for rated voltages from 1kV (Um =1.2 kV) up to 30 kV (Um =36 kV). Part 4: Test requirements on accessories for cables with rated voltages from 6kV (Um =7.2 kV) up to 30kV(Um=36kV)

Main technical parameters

Item Technical parameters
Rated voltage and frequency 26/35kV, 50Hz
Max peration voltage 40.5kV
Environment temperature -40℃~+40℃
Rated operating temperature of conductor 90℃
Max temperature of cable conductor at short circuit 250℃
AC voltage withstand test (117kV, 5min) NO breakdown or flashover
AC voltage withstand test (Wet, 104kV, 5min) NO breakdown or flashover
Impluse voltage test (95℃~100℃, ±200kV, 10times) NO breakdown or flashover
Heating cycle voliage test in air (Neither breakdown nor flashover shall occur during 60 cycles in air at the conductor temperature of 95℃~100℃ and 65kV) NO breakdown or flashover
Constant pressure load cyding test in water (Neither breakdown nor flashover shall occur during 30 cycles in air at the conductor temperature of 95℃~100℃ and 65kV) NO breakdown or flashover
Partial dischange test
- High temperature (95℃~100℃, 45kV)
- Ambient temperature (45kV)
s1.0pC
s1.0pC
Impluse voltage test (±200kV, 10times) NO breakdown or flashover
Power frequency voltage test (65kV, 15min) NO breakdown or flashover
Short circuit thermal stability test No damage
Short circuit thermal stability test No damage
Salt spray test(Spray rate: (0.4±0.1)L/(h-m³) Fog conductivity: (1600±200) mS/m; 11kV; 1000h NO breakdown or flashover
Humidity tst(Spray rate: (0.4±0.1)L/(h-m³) Fog conductivity: (70±10) mS/m; 11kV; 300h NO breakdown or flashover

26/35kV cold shrinkable XLPE cable accessories

Cross section Size of termination Ø of core insulation (d) Cable cross section (mm)
26/35kV Single core cold shrink outdoor termination kit WLS-1-26/35-50~120 50~120
WLS-1-26/35-150~300 150~300
WLS-1-26/35-400~630 400~630
/ /
Single core cold shrink indoor termination kit NLS-1-26/35-50~120 50~120
NLS-1-26/35-150~300 150~300
NLS-1-26/35-400~630 400~630
/ /
Single core cold shrink straight through joint JLS-1-26/35-50~120 50~120
JLS-1-26/35-150~300 150~300
JLS-1-26/35-400~630 400~630
/ /
3-cores cold shrink outdoor termination kit WLS-3-26/35-50~120 50~120
WLS-3-26/35-150~300 150~300
WLS-3-26/35-400~630 400~630
/ /
3-cores cold shrink indoor termination kit NLS-3-26/35-50~120 50~120
NLS-3-26/35-150~300 150~300
NLS-3-26/35-400~630 400~630
/ /
3-cores cold shrink straight through joint JLS-3-26/35-50~120 50~120
JLS-3-26/35-150~300 150~300
JLS-3-26/35-400~630 400~630
/ /

Keyword:

35kV Cold Shrinkable Cable Accessories

Get A Quote

Please provide the following valid information, and we will contact you as soon as possible.