66~110kV Composite Shell Outdoor Terminal
Description

Product Features
By epoxy pipe coated with silicone rubber umbrella skirt, casing with imported high quality liquid insulation filler, suitable for concentrated area to populated areas and electric equipment.
Safety explosion-proof, no injury and personne in and around electrical equipment.
Light weight, ease of installation.
The fouling resistance good, external insulation aging.
Main insulations'parts have been stipulated in the standard after testing in the factory.
Products Comply With The Following Standards
GB/T 11017.3-2014 Power cables with cross-linked polyethylene insulation and their accessories for rated voltage of 110kV (Um=126kV). Part 3: Accessories
IEC 60840-2011 Power cables with extruded insulation and their accessories for rated voltages above 30 kV (Um=36 kV) up to 150kV (Um=170kV). Test methods and requirements
Main technical parameters
| Item | Technical parameters |
| Rated voltage and frequency | 64/110kV, 50Hz |
| Max peration voltage | 126kV |
| Environment temperature | -40℃~+40℃ |
| Rated operating temperature of conductor | 90℃ |
| Max tomperature of cable conductor at short circuit | 250℃ |
| The cross section of the cable shall apply | 240~1600mm² |
| Apply the height of the altitude | s1000m (more than 1000 m can be separately designed) |
| Pollution level | Suitable for high polluted area (IV) high salt fog coastal areas |
| Partial dischange test (at ambient temperature, 96kV) | NO ddelectable discharge at the declared sensilivity (5pC or better) |
| Heating cycle voltage test (128kV, 95℃~100℃, heating 8h, cooling 16h) | Completed 20 cyclas |
| Partial dischange test (at high temperature, 96kV) | NO ddelectable discharge at the declared sensitivity (5pC or better) |
| Impluse voltage test followed by a power frequency voltage test - Impluse voltage test (95℃~100℃, ±550kV, 10tmes, respectively) - power frequency voltage test (160KV, 15min) |
NO breakdown or flashover NO breakdown or flashover |
| Power frecuency voltage test for cutdoor termination on (wet test, 185kV, 1min) | NO breakdown or flashover |
| Sealing test for the terminations assembled a.Press leakage test ((250±10)kPa, 1h) b.Vacuum leakage increase - Pressure increment (B-A) |
NO leakage of gas <2kPa |
| Voltage test on stand-off insulators - DC voltage test(25kV, 1min) - Lightning impluse voltage test (±37.5, 10min, respectively) |
NO breakdown or flashover NO breakdown or flashover |
| Raddio interference test for outdoor termination (81kV, 1Mhz) - RIV |
≤269μV |
Product size