66~110kV Prefabricated Dry Outdoor Cable Terminal
Description

Product Features
High quality of imported liquid silicone rubber, high strength, high elasticity, corona resistant, mark leakage resistance, ageing resistance.
No oil, explosion-proof, anti-seismic, light weight, maintenance-free.
Very convenient installation, flexible installation location, can be installed in vertical tilt.
External insulation ratio of leakage distance up to 35 mm/KV, and can provide the products for the special environment.
The stress cone surface at the top of product electric freld intensity, is covered by the umbrella skirt, to reduce the influence of external environment on the electric field distribution.
Main insulation parts have been tested according to the standard in the factory.
Products Comply With The Following Standards
GB/T11017.3-2014 Power cables with cross-linked polyethylene insulation and their accessories for rated voltage of 110kV (Um=126kV). Part 3: Accessories
IEC 60840-2011 Power cables with extruded insulation and their accessories for rated voltages above 30kV (Um = 36kV) up to150kV (Um=170kV). Test methods and requirements
Main technical parameters
| Item | Technical parameters |
| Rated voltage and frequency | 64/110kV, 50Hz |
| Max peration voltage | 126kV |
| Environment temperature | -40℃~+40℃ |
| Rated operating temperature of conductor | 90℃ |
| Max tomperature of cable conductor at short circuit | 250℃ |
| The cross section of the cable shall apply | 240~1600mm² |
| Apply the height of the altitude | ≤1000m (more than 1000 m can be separately designed) |
| Pollution level | Suitable for high polluted area (IV) high salt fog coastal areas |
| Partial dischange test (at ambient temperature, 96kV) | NO ddelectable discharge at the declared sensilivity (5pC or better) |
| Heating cycle voltage test (128kV, 95℃~100℃, heating 8h, cooling 16h) | Completed 20 cyclas |
| Partial dischange test (at high temperature, 96kV) | NO ddelectable discharge at the declared sensitivity (5pC or better) |
| Impluse voltage test followed by a power frequency voltage test - Impluse voltage test (95℃~100℃, ±550kV, 10tmes, respectively) - power frequency voltage test (160KV, 15min) |
NO breakdown or flashover NO breakdown or flashover |
| Power frecuency voltage test for cutdoor termination on (wet test, 185kV, 1min) | NO breakdown or flashover |
| Raddio interference test for outdoor termination (81kV, 1Mhz) - RIV |
≤301μV |