66~110kV Dry Plug-in type GIS terminal
Description

Product Features
The whole terminal is a dry structure, the inner is not filled with insulating oil, both environmental protection, and maintenance free.
The combination of spring, the stress cone surface close to the epoxy ring wall, can keep the interface pressure constant term.
Easy installation, no need to charge six sulfur fluoride gas.
The main insulation parts have been tested in the factory according to the standard.
Products Comply With The Following Standards
GB/T 11017.3-2014 Power cables with cross-linked polyethylene insulation and their accessories for rated voltage of 110kV (Um=126kV). Part 3: Accessories
IEC 60840-2011 Power cables with extruded insulation and their accessories for rated voltages above 30kV (Um=36kV) up to150 kV( Um=170kV). Test methods and requirements
IEC 62271-209-2007 High-voltage switchgear and controlgear. Part 209: Cable connections for gas-insulated metal-enclosed switchgear for rated voltages above 52kV. Fluid-filled and extruded insulation cables. Fluid-flled and dry-type cable-terminations
GB/T 22381-2008 Cable connections for gas-insulated metal-enclosed switchgear for rated voltages of 72.5kV andabove. Fluid-flled and extruded insulation power cables. Fluid-filled and dry type cable-terminations
Main technical parameters
| Item | Technical parameters |
| Rated voltage and frequency | 64/110kV, 50Hz |
| Max peration voltage | 126kV |
| Environment temperature | -40℃~+40℃ |
| Rated operating temperature of conductor | 90℃ |
| Max temperature of cable conductor at short circuit | 250℃ |
| The cross section of the cable shall apply | 240~1600mm² |
| Partial dischange test (at ambient temperature, 96kV) | NO ddelectable discharge at the declared sensitivity (5pC or better) |
| Heating cycle voltage test (128kV, 95℃~100℃, heating 8h, cooling 16h) | Completed 20 cycles |
| Partial dischange test(at high temperature,96kV) | NO ddelectable discharge at the declared sensitivity (5pC or better) |
| Impluse voltage test followed by a power frequency voltage test - Impluse voltage test (95℃~100℃, ±550kV, 10times, respectively) - Power frequency voltage test (160kV, 15min) |
NO breakdown or flashover NO breakdown or flashover |
| Sealing test for the terminations assembled a. Press leakage test ((250±10)kPa, 1h) b. Vacuum leakage increase - Pressure increment(B-A) |
NO leakage of gas <2kPa |