CONTACT US
Jiangsu Shitate Intelligent Power Co.,LTD.
E-Mail: sttxs@jsshitate.com
Telephone: +86-18852493399
Telephone: +86-18626077857
Address: No. 5 Datian Road, Guanlin Town, Yixing City
220kV Composite Shell Outdoor Terminal
Description

Product Features
Epoxy pipe coated with silicone rubber umbrella skirt, flexible composite insulation material security riot, can ensure the safety of the electrical equipment and personnel around, suitable for centralized place to populated areas and electricequipment.
Composite tube light weight, convenient transportation and installation.
Stress cone using imported high elastic liquid silicone rubber, and carry on finite element optimization design, effectively solve the problem of electric feld stress concentration.
Excellent hydrophobic properties and creepage resistance, arc resistance, good weatherability and the fouling resistance, unfavorable external insulation aging.
Main insulation parts have been stipulated in the standard after testing in the factory.
Products Comply With The Following Standards
GB/T 18890.3-2015 Power cables with cross-linked polyethylene insulation and their accessories for rated voltage of 220kV (Um=252kV). Part 3: Accessories
IEC 62067-2011 Power cables with extruded insulation and their accessories for rated voltages above 150kV (Um=170kV) up to 500kV (Um=550kV). Test methods and requirements
Main technical parameters
| Item | Technical parameters |
| Rated voltage and frequency | 127/220kV, 50Hz |
| Max peration voltage | 252kV |
| Environment temperature | -40℃~+40℃ |
| Rated operating temperature of conductor | 90℃ |
| Max temperature of cable conductor at short circuit | 250℃ |
| The cross section of the cable shall apply | 240~2500mm² |
| Apply the height of the altitude | ≤1000m (more than 1000m can be separately designed) |
| Pollution level | Suitable for high polluted area (IV) high salt fog coastal areas |
| Partial dischange test (at ambient temperature, 190kV) | NO ddelectable discharge at the declared sensitivity (5pC or better) |
| Heating cycle voltage test (254kV, 95℃~100℃, heating 8h, cooling 16h) | Completed 20 cycles |
| Partial dischange test (at high temperature, 190kV) | NO ddelectable discharge at the declared sensitivity (5pC or better) |
| Impluse voltage test followed by a power frequency voltage test - Impluse voltage test (95℃~100 C, ±1050kV, 10times, respectively) - Power frequency voltage test (254kV, 15min) |
NO breakdown or flashover NO breakdown or flashover |
|
Sealing test for the terminations assembled |
NO leakage of gas |
Product size

Keyword:
220kV Composite Shell Outdoor Terminal
Get A Quote
Please provide the following valid information, and we will contact you as soon as possible.